Satronic DKW 976

Technical data:

  • 2-stage with preheater bridging contact
  • Operating voltage 220 / 240 V (-15…+10%), 50 Hz (± 5%) or
  • 110 /120 V (-15…+10%), 60 Hz (± 5%)
  • Fuse rating 10 A fast, 6 A slow
  • Power consumption approx. 12 VA
  • Maximum load per terminal
  • Reset time from lock out: none

Description

The oil burner safety control boxes DKW 976-N model 05 control and supervise forced draught burners (with or without oil preheater) on direct air heaters and for burners with an oil consumption over 30 kg/h. They are certified and approved according to the applicable European standards.