Description
Product Types
The chart below is an overview of the characteristics for a sampling of large rectifier transformer:
Type | 74MVA/110kV | 134.05MVA/330kV | 70.5MVA/220kV | 106.26MVA/220kV | 140MVA/220kV | 136.2MVA/330kV |
Capacity (MVA) | 74 | 134 | 71 | 106 | 140 | 136 |
DC Voltage (V) | 70 | 1230 | 880 | 1220 | 1350 | 1300 |
DC Current (A) | 2×45000 | 2×46000 | 2×34000 | 2×37000 | 2×44000 | 2×44000 |
Number of Pulses | 12 | 12 | 12 | 12 | 12 | 12 |
Technical Data of 10kV Epoxy-resin Insulation Dry-type Transformer
Rated
Capacity (KVA) |
Voltage Combined | Vector-group | No-load
Loss(W) |
75℃ Load
Loss(W) |
No-load
Current(%) |
Short-circuit
Impendance(%) |
||
HV(kV) | Tapping
Ranges |
LV(kV) | ||||||
30 | 6
6.3 6.6 10 10.5 11 |
±5%
±2×2.5% |
0.4 | Dyn11
Yyn0 |
190 | 710 | 2.4 | 4 |
50 | 270 | 1000 | 2.4 | |||||
80 | 370 | 1380 | 1.8 | |||||
100 | 400 | 1570 | 1.8 | |||||
125 | 470 | 1850 | 1.6 | |||||
160 | 540 | 2130 | 1.6 | |||||
200 | 620 | 2530 | 1.4 | |||||
250 | 720 | 2760 | 1.4 | |||||
315 | 880 | 3470 | 1.2 | |||||
400 | 980 | 2990 | 1.2 | |||||
500 | 1160 | 4880 | 1.2 | |||||
630 | 1340 | 5880 | 1.0 | |||||
630 | 1300 | 5960 | 1.0 | 6 | ||||
800 | 1520 | 6960 | 1.0 | |||||
1000 | 1770 | 8130 | 1.0 | |||||
1250 | 2090 | 9690 | 1.0 | |||||
1600 | 2450 | 11730 | 1.0 | |||||
2000 | 3050 | 14450 | 0.8 | |||||
2500 | 3600 | 17170 | 0.8 | |||||
1600 | 2450 | 12960 | 1.0 | 8 | ||||
2000 | 3050 | 15960 | 0.8 | |||||
2500 | 3600 | 18890 | 0.8 |
Technical Data of 20kV Epoxy-resin Insulation Dry-type Transformer
Rated Capacity
(KVA) |
Voltage Combined | Vector-group | No-load Loss(W) | 75℃ Load Loss(W) | No-load Current(%) | Short-circuit
Impendance(%) |
||
HV(kV) | Tapping
Ranges |
LV(kV) | ||||||
50 | 20
22 24 |
±5%
±2×2.5% |
0.4 | Dyn11
Yyn0 |
380 | 1300 | 2.4 | 6 |
100 | 600 | 2100 | 2.2 | |||||
160 | 750 | 2600 | 1.8 | |||||
200 | 820 | 3100 | 1.8 | |||||
250 | 940 | 3600 | 1.6 | |||||
315 | 1080 | 4300 | 1.6 | |||||
400 | 1280 | 5100 | 1.4 | |||||
500 | 1500 | 6100 | 1.4 | |||||
630 | 1700 | 7200 | 1.2 | |||||
800 | 1950 | 8700 | 1.2 | |||||
1000 | 2300 | 10300 | 1.0 | |||||
1250 | 2650 | 12150 | 1.0 | |||||
1600 | 3100 | 14600 | 1.0 | 8 | ||||
2000 | 3600 | 17250 | 0.8 | |||||
2500 | 4300 | 20400 | 0.8 | |||||
2000 | 3600 | 18800 | 0.8 | |||||
2500 | 4300 | 22400 | 0.8 |
Technical Data of 10kV Epoxy-resin Insulation Dry-type Transformer
Rated
Capacity (KVA) |
Voltage Combined | Vector-group | No-load
Loss(W) |
Load loss under different insulation
and heat resistance grades(W) |
No-load
Current(%) |
Short-circuit
Impendance(%) |
||||
HV(kV) | Tapping
Ranges |
LV(kV) | B(100℃) | P(120℃) | H(145℃) | |||||
30 | 6
6.3 6.6 10 10.5 11 |
±5%
±2×2.5% |
0.4 | Dyn11
Yyn0 |
135 | 605 | 640 | 685 | 4.0 | |
50 | 195 | 845 | 900 | 965 | ||||||
80 | 265 | 1160 | 1240 | 1330 | ||||||
100 | 290 | 1330 | 1415 | 1520 | ||||||
125 | 340 | 1565 | 1665 | 1780 | ||||||
160 | 385 | 1800 | 1915 | 2050 | ||||||
200 | 445 | 2135 | 2275 | 2440 | ||||||
250 | 515 | 2330 | 2485 | 2665 | ||||||
315 | 635 | 2945 | 3125 | 3355 | ||||||
400 | 705 | 3375 | 3591 | 3850 | ||||||
500 | 835 | 4130 | 4390 | 4705 | ||||||
630 | 965 | 4975 | 5290 | 5660 | ||||||
630 | 935 | 5050 | 5365 | 5769 | 6.0 | |||||
800 | 1095 | 5895 | 6265 | 6715 | ||||||
1000 | 1275 | 6885 | 7315 | 7885 | ||||||
1250 | 1505 | 8190 | 8720 | 9335 | ||||||
1600 | 1765 | 9945 | 10555 | 11320 | ||||||
2000 | 2195 | 12240 | 13005 | 14005 | ||||||
2500 | 2590 | 14535 | 15455 | 16605 | ||||||
1600 | 1765 | 11050 | 11660 | 12510 | 8.0 | |||||
2000 | 2195 | 13520 | 14360 | 15400 | ||||||
2500 | 2950 | 15980 | 17000 | 18260 |